The fire main

International shore connection

also: ISC

A standardised coupling through which a shore fire brigade (or another ship) feeds water into the fire main when the ship’s own pumps are dead.

Key facts

Technical parameters
Flange outer diameter
178 mm
Inner diameter
64 mm
Bolt circle diameter
132 mm, 4 holes of 19 mm slotted to the edge
Flange thickness
at least 14.5 mm
Bolts
4 bolts of 16 mm diameter and 50 mm length, with nuts and washers
Working pressure
1.0 MPa

On the fire control plan

These are not bulkhead signs: a system is marked with its symbol on the fire control plan (IMO res. A.1116(30), table 3).

Legal basis

SOLAS II-2/10.2.1.7 and FSS Code chapter 2.

This is not a legal text: when in doubt, the current wording of the Convention and the FSS Code decides.